End of Line Termination Concept Most of the buses we use are specified with end of line termination in mind. In the field these terminations are not always present, especially in short runs. Do we need them? Here’s an analogy I like that illustrates why we need end of line terminations: a bus behaves like…
By
Matthew Scheffel
A BACnet Instance Number Is a Globally-unique Address An often misunderstood and neglected topic is the BACnet instance number of a BACnet device. Neglecting to think about this number at installation might not bite you today, but it remains as technical debt that complicates future work. It’s a number that identifies a device uniquely on…
By
Matthew Scheffel
I encountered an RS-422 bus for the first time recently and it threw me through a bit of a loop! The device was a Modbus/RTU slave device and so I anticipated a RS-485 connection as per usual, but that was not the case. It’s the same cable, and the same essential signalling standard, but if…
By
Matthew Scheffel
Low-voltage communication buses are critical to networked automation systems and when they fail they are a pain to troubleshoot. We use them because the cables are cheap and you don’t need expensive switches, but what you save in parts you may pay in labor later. Ethernet/IP based communication is on the rise, but is still…
By
Matthew Scheffel
When installers build automation systems getting it working is their main focus. They see building automation security as an obstacle to overcome rather than the goal. If authentication is getting in the way, they disable it. When firewalls are blocking communication, they disable that too. Even more problematic is the fact that several popular automation…
By
Matthew Scheffel
I submitted a link to this site to AutomatedBuildings.com and Ken Sinclair got back to me with an interview request! You have find the interview in their April 2016 issue, here. In it we discuss in broad terms what this site is about and my plan for it going forward. Here’s a snippet: Sinclair: Is…
By
Matthew Scheffel
RS-485 bus grounding and termination seems like a magical ritual. Some people get lazy with the details of termination because buses often work even when termination is done incorrectly. I had some untwisted, shielded AWG22 lying around, so I used it to show a quick comparison between bus wiring in a controlled environment. I used…
By
Matthew Scheffel
BACnet networks are getting big. Their network infrastructure is getting complicated. BACnet is used to connect campuses, not just buildings. When you connect several networks together, a BACnet/IP Broadcast Management Device (BBMD) is necessary to bridge them. They’re important, but often misunderstood. Use them wrong, and you’ll get a broadcast storm. What Are Broadcasts? Broadcasts…
By
Matthew Scheffel
Modbus is one of the simpliest protocols you’ll find in the field. It’s the closest protocol “to the metal” of the chip on a controller since it often just directly exposes the controller’s memory. There’s no point discovery here; there are no point names or descriptions to help you integrate. All you have are datasheets…
By
Matthew Scheffel
RS-485 grounding is frequently missing from commercial automation installations. It’s especially egregious when you are using your shield as your signal reference, because that reference is now noisy as heck. The shield’s job to collect interference. It’s up to you to make sure that interference goes somewhere. The Case Study I was looking at the…